Search results for "Overhead cable"

showing 4 items of 4 documents

Improving angle stability by switching shunt reactors in mixed overhead cable lines. An Italian 400 kV case study

2019

Stringent environmental constraints make the construction of new transmission overhead lines more and more difficult. Alternatively, today it is possible to use cable lines for high (HV) and extra-high (EHV) voltage systems. The configuration of the so-called mixed lines can create some problems in the operation of the electrical system, both during steady-state and transient conditions. In particular, the system stability is one of the main concerns when analyzing the dynamic response of power systems. In this paper, the study of angular stability of a system containing a mixed line is presented: a specific control logic applied to the shunt reactors of the mixed line is proposed as improv…

Control and OptimizationMixed lineComputer scienceEnergy Engineering and Power Technologysystem stability; mixed line; cable; shunt reactor; switching; dynamic analysis; dynamic equivalent; Sicily; Italy; continental Europelcsh:TechnologyDynamic analysilaw.inventionElectric power systemSystem stabilitylawControl theoryElectrical and Electronic EngineeringControl logicEngineering (miscellaneous)SicilyDynamic equivalentlcsh:TRenewable Energy Sustainability and the EnvironmentContinental Europedynamic analysisSettore ING-IND/33 - Sistemi Elettrici Per L'EnergiaTransmission (mechanics)ItalyShunt reactorOverhead cableSwitchingShunt reactorShunt (electrical)Energy (miscellaneous)VoltageCable
researchProduct

Efficient modeling of a combined overhead cable line for grounding-system analysis

2008

Simple compact models for combined overhead-cable lines supplying a substation are presented as an extension of a previous paper for grounding system analysis. The overhead line section can be equipped with uniform or combined ground wires, whereas the cable line section can consist of coated metal sheathed cables, with/without intermediate grounding, or uncoated metal sheathed cables in continuous contact with the earth. Besides the calculation of the earth current at the faulted substation, the proposed modeling method allows the evaluation of the leakage current at the transition station, where cables are connected to the overhead line, as well as at critical overhead line towers. In thi…

EngineeringDesign stageComputer programGroundbusiness.industryGrounding systemElectrical engineeringEarthing systemLine (electrical engineering)law.inventionSettore ING-IND/33 - Sistemi Elettrici Per L'EnergiaCable lineSettore ING-IND/31 - ElettrotecnicalawOverhead cableElectronic engineeringcombined overhead cable linesbusinessOverhead line
researchProduct

A Simple Method for Evaluating Ground-Fault Current Transfer at the Transition Station of a Combined Overhead-Cable Line

2008

When a substation is fed by a combined overhead-cable transmission line, a significant part of the ground fault current flows through cable sheaths and is discharged into the soil at the transition station where cables are connected to the overhead line. Such a phenomenon, known as ldquofault application transfer,rdquo may result in high ground potentials at the transition station which may cause shocks and equipment damage. The scope of this paper is to present new analytic formulas which can be used for the direct calculation of the fault current transferred at the transition station and its ground potential rise as well as the substation earth current. The proposed formulas allow evaluat…

EngineeringGroundbusiness.industryElectric shockAerial cableElectrical engineeringEnergy Engineering and Power TechnologyFault application transfer ground fault current distribution grounding safety conditions.medicine.diseaseFault (power engineering)Line (electrical engineering)law.inventionlawTransmission lineOverhead cablemedicineElectrical and Electronic EngineeringbusinessOverhead line
researchProduct

Ground-Fault Current Transfer at the Transition Station of a Combined Overhead-Cable Line. A Parametric Analysis

2007

When a substation is fed by a combined overhead-cable transmission line, a significant part of the ground fault current flows through the grounded cable sheaths and discharges into the earth at the transition station, where cables are connected to the overhead line. If the transition station is a dead-end steel pole structure, the local ground electrode, small and of high resistance, could be inadequate to maintain the ground potential rise within safety limits in case of a fault to ground at the receiving end substation. Based on a circuit model approach, the paper presents a parametric analysis of the fault current distribution between the faulted substation and the transition station, ta…

EngineeringParametric analysisbusiness.industryElectrical engineeringFault (power engineering)Line (electrical engineering)law.inventionSettore ING-IND/33 - Sistemi Elettrici Per L'EnergiaTransmission linelawTransfer (computing)Overhead cableSubstations Fault currents Circuit faults Power overhead lines Power cables Cable shielding Satellite ground stations Steel Electrodes SafetyCurrent (fluid)businessComputer Science::Operating SystemsOverhead line
researchProduct